SV01M
Troubleshooting and Diagnostics
Fault Cause Remedy
(1)
O
Output fault:
Transistor fault
Output short circuit Check motor/motor cable
Acceleration time too short Increase P104, P125
Severe motor overload, due to:
Mechanical problem
Drive/motor too small for application
Check machine / system
Verify drive/motor are proper size for
application
Boost values too high Decrease P168, P169
Excessive capacitive charging current of
the motor cable
Use shorter motor cables with lower charging
current
Use low capacitance motor cables
Install reactor between motor and drive.
Failed output transistor Contact factory technical support
Output fault: Ground fault Grounded motor phase Check motor and motor cable
Excessive capacitive charging current of
the motor cable
Use shorter motor cables with lower charging
current
P
Motor Overload fault Excessive motor load for too long Verify proper setting of P108
Verify drive and motor are proper size for
application
Flying Restart fault Controller was unable to synchronize with
the motor during restart attempt; (P110
= 5 or 6)
Check motor / load
Single-Phase fault A mains phase has been lost Check mains voltage
U
Start fault Start command was present when power
was applied (P110 = 0 or 2).
Must wait at least 2 seconds after power-up
to apply Start command
Consider alternate starting method (P110).
TB5 (0-10V signal)
Threshold fault
0-10V signal (at TB5) drops below the value
set in P158.
Check signal/signal wire
Refer to parameters P157 and P158
(1) The drive can only be restarted if the error message has been reset.