SV01M
Commissioning
Code Possible Settings
IMPORTANT
No. Name Default Selection
p
Proportional Gain 5.0 0.0 {%} 1000.0 Used to tune the PID loop:
Increase P207 until system becomes unstable,
then decrease P207 by 10-15%
Next, increase P208 until feedback matches
setpoint
If required, increase P209 to compensate for
sudden changes in feedback
p
Integral Gain 0.0 0.0 {s} 20.0
Derivative Gain 0.0 0.0 {s} 20.0
NOTE
Derivative Gain is very sensitive to noise on the feedback signal. Use with care.
Derivative Gain is not normally required in pump and fan applications
PID Setpoint Ramp 20.0 0.0 {s} 100.0 time of setpoint change from P204 to P205
or vice versa.
Used to smooth the transition from one PID
setpoint to another, such as when using the
Preset PID Setpoints (P231...P233)
p
Minimum Alarm 0.0 P204 P205 Use with P140, P142 = 18...23
P
Maximum Alarm 0.0 P204 P205
Preset PID Setpoint #1 0.0 P204 P205 TB-13A activated; P121 = 3 and P200 = 1 or 2
P
Preset PID Setpoint #2 0.0 P204 P205 TB-13B activated; P122 = 3 and P200 = 1 or 2
Preset PID Setpoint #3 0.0 P204 P205 TB-13C activated; P123 = 3 and P200 = 1 or 2
Preset PID Setpoint #4 0.0 P204 P205 TB-13D activated; P124 = 3 and P200 = 1 or 2
P
Sleep Threshold 0.0 0.0 {Hz} 500.0 If drive speed < P240 for longer than P241,
output frequency = 0.0 Hz; drive display =
P240 = 0.0: Sleep mode is disabled.
P200 = 0…2: Drive will start again when speed
command is above P240
P242 > 0.0: Drive will restart when the PID
feedback differs from the setpoint by more
than the value of P242 or when the PID loop
requires a speed above P240.
Sleep Delay 30.0 0.0 {s} 300.0
P
Sleep Bandwidth 0.0 0.0 B
max
Where: B
max
= |(P205 - P204)|
43
Feedback Sleep
Entry Threshold
0.0 P204 P205 Active only when P244 = 1 or 2
44
Sleep Entry Mode 0 0 Enter SLEEP if Drive Speed <P240 For time longer than P241
1 Enter SLEEP if Feedback >P243 For time longer than P241 or same as Sel 0
2 Enter SLEEP if Feedback <P243 For time longer than P241 or same as Sel 0
45
Sleep Entry Stop
Type
0 0 Coast to Stop
1 Ramp to Stop
2 Stop with P111 settings
4
Feedback Recovery
from Sleep Threshold
0.0 P204 P205 Active only when P247 = 1 or 2
47
Sleep Recovery
Mode
0 0 Recovery if Speed Setpoint > P240
or if PID feedback differs from setpoint
by more than P242
1 Recovery only if Feedback < P246
2 Recovery only if Feedback > P246
(2) Parameter applicable to SMV models 15HP (11kW) and higher.