27
SV01M
Commissioning
Code Possible Settings
IMPORTANT
No. Name Default Selection
0
Minimum Frequency 0.0 0.0 {Hz} P103 • P102, P103 are active for all speed
references
• When using an analog speed
reference, also see P160, P161
Maximum Frequency 60.0 7.5 {Hz} 500
NOTE
• P103 cannot be set below Minimum Frequency (P102)
• To set P103 above 120 Hz:
- Scroll up to 120 Hz; display shows
(flashing).
- Release s button and wait one second.
- Press s button again to continue increasing P103.
WARNING!
Consult motor/machine manufacturer before operating above rated frequency. Overspeeding the motor/machine may cause
damage to equipment and injury to personnel!
Acceleration Time 1 20.0 0.0 {s} 3600 • P104 = time of frequency change from 0 Hz to
P167 (base frequency)
• P105 = time of frequency change from P167
to 0 Hz
• For S-ramp accel/decel, adjust P106
Deceleration Time 1 20.0 0.0 {s} 3600
EXAMPLE: IF P103 = 120 Hz, P104 = 20.0 s and P167 (base frequency) = 60 Hz; then the rate of frequency change from 0
Hz to 120 Hz = 40.0 s
S-Ramp Integration
Time
0.0 0.0 {s} 50.0 • P106 = 0.0: Linear accel/decel ramp
• P106 > 0.0: Adjusts S-ramp curve for smoother
ramp
7
(1)
Line Voltage Selection 1* 0 Low (120, 200, 400, 480VAC) * The default setting is 1 for all drives except
when using “Reset to 50Hz default settings”
(Parameter P199, selection 4) with 480V
models. In this case, the default setting is 0.
1 High (120, 240, 480, 600VAC)
Motor Overload 100 30 {%} 100 P108 = motor current rating x 100
SMV output rating
Example: if motor = 3amps and SMV = 4amps,
then P108 = 75%
NOTE
Do not set above rated motor current as listed on the motor dataplate. The motor thermal
overload function of the SMV is UL approved as a motor protection device. Cycling power after
an overload fault could result in significantly reducing the motor life.
Motor Overload Type 0 0 Speed Compensation
Ir
100%
60%
30 f
1
0
V0108
1 No Speed Compensation
Example: Motor is cooled by forced
ventilation as apposed to shaft mounted,
self cooling fans.
(1) Any changes to this parameter will not take effect until the drive is stopped.
Kommentare zu diesen Handbüchern