SV01M
Commissioning
4.5.7 Diagnostic Parameters
Code
Display Range (READ ONLY) IMPORTANT
No. Name
Fault History Displays the last 8 faults
Format: n.xxx where: n = 1..8,
1 is the newest fault; xxx = fault message (w/o the
.)
Refer to section 5.3
Software Version Format: x.yz
Drive ID A flashing display indicates that the Drive ID stored in the EPM
does not match the drive model it is plugged into.
P
Internal Code Alternating Display: xxx-; -yy
DC Bus Voltage 0 {VDC} 1500
Motor Voltage 0 {VAC} 1000
P
Load 0 {%} 255 Motor load as % of drive’s output current rating.
Refer to section 2.3.
Motor Current 0.0 {A} 1000 Actual motor current
Torque 0 {%} 500 Torque as % of motor rated torque (vector mode only)
P
Output Power kW 0.00 {kW} 650.0
Total kWh 0.0 {kWh} 9999999 Alternating display: xxx-; yyyy when value exceeds 9999
P
Heatsink Temp 0 {°C} 150 Heatsink temperature
0-10 VDC Input 0.0 {VDC} 10.0 Actual value of signal at TB-5 (See P162)
4-20 mA Input 0.0 {mA} 20.0 Actual value of signal at TB-25 (See P162)
TB-5 Feedback P204 P205 TB-5 signal value scaled to PID feedback units (See P162)
TB-25 Feedback P204 P205 TB-25 signal value scaled to PID feedback units (See P162)
Network Feedback P204 P205 Network signal value scaled to PID feedback units
Analog Output 0 {VDC} 10.0 Refer to P150…P155
Actual Output
Frequency
0 {Hz} 500.0
Network Speed
Command
0 {Hz} 500.0 Command speed if (Auto: Network) is selected as the speed
source
Terminal and
Protection Status
Indicates terminal status using segments of the LED display.
(Refer to section 4.5.7.1)
Keypad Status Indicates keypad button status using segments of the LED
display. (Refer to section 4.5.7.2)
Total Run Time 0 {h} 9999999 Alternating display: xxx-; yyyy when value exceeds 9999
Total Power On Time 0 {h} 9999999
Fault History 1 8 Displays the last 8 faults
Format: n.xxx where: n = 1..8,
1 is the newest fault; xxx = fault message (w/o the .)
Refer to section 5.3
P
Fault History Time 0 {h} 999999 Display: “n.hh-” “hhhh” “mm.ss” = fault #, hours, seconds
The “hhhh” screen is displayed after hours exceed 999.
Fault History Counter 0 255 Number of sequential occurrences of a fault.
For example: 3 external faults occur over a period of time
with no other errors occurring. Then P552 will indicate 3,
P550 will indicate the error EF and P551 will indicate the
time of the first fault occurrence.