Commissioning
Code Possible Settings
IMPORTANT
No. Name Default Selection
Segment #9
Segment #9
Frequency Setpoint
0.0 -500.0 {Hz} 500.0 If P112 = 1, negative sign forces reverse
direction
1
Segment #9
Accel/Decel Time
20.0 0.0 {sec} 3600.0
2
Segment #9
Time in current step
0.0
0
0.0 {P708} 6553.5
0 {P708} 65535
Scaling/units depend on P708
Skip segment if time = 0
Segment #9
Digital Output State
0
Value set in P753 0 1 2 3 4 5 6 7
Relay (Bit 0) 0 1 0 1 0 1 0 1
TB14 (Bit 1) 0 0 1 1 0 0 1 1
I/O option Relay (Bit 2)
0 0 0 0 1 1 1 1
NOTE: P441 is the Relay Output (TB-19, 20, 21) of the
optional Digital I/O module (ESVZAL0, ESVZAL1).
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must be
set to accept data from the sequencer: P140,
P142, P441 = 27
Segment #9 TB30
Analog Output
Value
0.00 0.00 {VDC} 10.00 TB30 configuration parameter must be set to
accept this value: P150 = 10
Segment #10
Segment #10
Frequency Setpoint
0.0 -500.0 {Hz} 500.0 If P112 = 1, negative sign forces reverse
direction
Segment #10
Accel/Decel Time
20.0 0.0 {sec} 3600.0
7
Segment #10
Time in current step
0.0
0
0.0 {P708} 6553.5
0 {P708} 65535
Scaling/units depend on P708
Skip segment if time = 0
Segment #10
Digital Output State
0
Value set in P758 0 1 2 3 4 5 6 7
Relay (Bit 0) 0 1 0 1 0 1 0 1
TB14 (Bit 1) 0 0 1 1 0 0 1 1
I/O option Relay (Bit 2)
0 0 0 0 1 1 1 1
NOTE: P441 is the Relay Output (TB-19, 20, 21) of the
optional Digital I/O module (ESVZAL0, ESVZAL1).
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must
be set to accept data from the sequencer:
P140, P142, P441 = 27
Segment #10 TB30
Analog Output
Value
0.00 0.00 {VDC} 10.00 TB30 configuration parameter must be set to
accept this value: P150 = 10
Segment #11
Segment #11
Frequency Setpoint
0.0 -500.0 {Hz} 500.0 If P112 = 1, negative sign forces reverse
direction
1
Segment #11
Accel/Decel Time
20.0 0.0 {sec} 3600.0
Segment #11
Time in current step
0.0
0
0.0 {P708} 6553.5
0 {P708} 65535
Scaling/units depend on P708
Skip segment if time = 0
Segment #11
Digital Output State
0
Value set in P763 0 1 2 3 4 5 6 7
Relay (Bit 0) 0 1 0 1 0 1 0 1
TB14 (Bit 1) 0 0 1 1 0 0 1 1
I/O option Relay (Bit 2)
0 0 0 0 1 1 1 1
NOTE: P441 is the Relay Output (TB-19, 20, 21) of the
optional Digital I/O module (ESVZAL0, ESVZAL1).
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must be
set to accept data from the sequencer: P140,
P142, P441 = 27
Segment #11 TB30
Analog Output
Value
0.00 0.00 {VDC} 10.00 TB30 configuration parameter must be set to
accept this value: P150 = 10